This question is based on our three-node network where allresistances are equal. Generators are located at nodes 1 and 2,while the customer is located at node 3.
Power flows through the network are:
F(1,3) = 44 MW
F(2,3) = 56 MW
F(1,2) = -12 MW (i.e., 12 MW from node 2 to node 1)
The transmission limit on Line (1,2) is 10 MW in eitherdirection, so the line is overloaded by 2 MW. Assume that lines(2,3) and (1,3) can carry a very large amount of power, so thatthey will never be congested. Calculate the adjustment forGenerator 1 that relieves the transmission congestion on line(1,2).
If you find that Generator 1 should increase output to relievethe congestion, then enter your response as a positive number. Ifyou find that Generator 1 should decrease output to relieve thecongestion, then enter your response as a negative number.